SINUS SYSTEM HYDRONIC UNIT
Hydronic Junction with Sinus Manifold Type 80/60
Hot water flow rate: | 3.0 m³/h (13.2 gpm) |
Pipe distance (OC): | 125 mm (4 11/16") pump groups |
product description:
- For (condensing) boilers with low water content
- Application for roof centres possible (On-Top-Assembly)
- Hydronic decoupling by means of additional junction
- No hydronic problems with multiple heating circuits
- Flawless operation
- Built-in air purger and sediment drain
- Left of right hand assembly
- Extremely short assembly time (no piping)
- Hydronic junction with directly welded sinus mani fold made of square profiles 80/50, 37-2 steel with welded endpieces.
-
Hydronic junctions consisting of a vertical, rectangular chamber with two lateral 1 1/4" NPT-threaded pipe nipples for the connection of the heat source as well as 1/2" couplings for air purging, sensor and draining. 1" NPT thread for connecting the heating circuits.
- Sinus manifold as combined flow and return manifold with adjacent chambers divided by a sinusoidal parting wall.
- Connection of junction and manifold by directly welded flow pipe; connection of return pipe by square profile running vertically parallel to the junction.
- Additional 1/2" coupling in the lower secondary flow pipe.
- The SINUS HYDRONIC UNIT was pressure tested and primed in our factory.
- Wall thickness 2.5 mm (1/10").
- Application range: maximum operation temperature 90 °C (194 ºF).
- Operation pressure: Maximum 4 bar (60 psi).
- Left or right hand assembly.
- Available for two to five heating circuits.

Accessories
Prefabricated Insulation
According to the German agreement 
on heating plants (EnEV).
40 mm (1 9/16") PUR foam in aluminum casing.
Consists of 2 half shells with end pieces
and cut outs.
Wall Mounting Bracket (set of 2)
Sound proofed and galvanized. 
Consists of one wall plate and
support arm.